Repeat for each unit. Each one asks:
Type of unit*Choose one
Unit or asset referenceShort answer
Position in this areaShort answer
Is this unit on the roof or outside?Yes or No
Where is the unit?Short answer
Mark it standing beside the unit, so the next engineer finds the right one on a busy roof. Tap Mark current location at the unit. It saves the coordinates, a grid reference and the accuracy.
Shown when “Is this unit on the roof or outside?” is Yes
ManufacturerShort answer
ModelShort answer
Serial numberShort answer
Photos before the workPhotos
FiltersChoose one
CoilsChoose one
Condensate drain and pumpChoose one
- CheckCondensate problem. A blocked drain or failed pump can overflow onto ceilings and electrics.
Shown when “Condensate drain and pump” is “Blocked or leaking”
Fans and beltsChoose one
Electrical connections and controlsChoose one
Supply air or flow temperature (°C)Number
Return air or return temperature (°C)Number
Temperature difference, return minus supply (°C)Worked out by the form
Shown when “Supply air or flow temperature (°C)” is answered and “Return air or return temperature (°C)” is answered
Expected difference, lowest (°C)Number
From the commissioning record or the maker's data for this mode. The form compares the reading with it; it sets no figure.
Expected difference, highest (°C)Number
Difference against the expected rangeWorked out by the form
Shown when “Supply air or flow temperature (°C)” is answered and “Return air or return temperature (°C)” is answered and “Expected difference, lowest (°C)” is answered and “Expected difference, highest (°C)” is answered
Does this unit hold F gas refrigerant?Yes or No
Refrigerant, from the labelShort answer
Shown when “Does this unit hold F gas refrigerant?” is Yes
Charge (kg)Number
Shown when “Does this unit hold F gas refrigerant?” is Yes
Global warming potential of the gasNumber
From the label or the data sheet.
Shown when “Does this unit hold F gas refrigerant?” is Yes
Carbon dioxide equivalent (tonnes)Worked out by the form
Shown only when the answers above make it relevant
Is the unit labelled as hermetically sealed?Yes or No
Shown when “Does this unit hold F gas refrigerant?” is Yes
Is a leak detection system fitted?Yes or No
Shown when “Does this unit hold F gas refrigerant?” is Yes
- GuidanceUnder 5 tonnes. The F gas rules do not require leak checks for this unit.
Shown only when the answers above make it relevant
- GuidanceHermetically sealed and under 10 tonnes. The F gas rules do not require leak checks for this unit, as long as it is labelled as hermetically sealed.
Shown only when the answers above make it relevant
- Check5 tonnes or more, under 50. Leak checks are due at least once every 12 months, or every 24 months where a leak detection system is fitted.
Shown only when the answers above make it relevant
- Check50 tonnes or more, under 500. Leak checks are due at least once every 6 months, or every 12 months where a leak detection system is fitted.
Shown only when the answers above make it relevant
- Warning500 tonnes or more. Leak checks are due at least once every 3 months, or every 6 months with a leak detection system. Equipment of this size must have a leak detection system that alerts the operator or a service company.
Shown only when the answers above make it relevant
Date of the previous leak check, from the F gas recordDate
Shown when “Does this unit hold F gas refrigerant?” is Yes
Days since the previous leak checkWorked out by the form
Shown when “Does this unit hold F gas refrigerant?” is Yes and “Date of the previous leak check, from the F gas record” is answered and “Date of visit” is answered
Was a leak check done on this visit?Yes or No
Shown when “Does this unit hold F gas refrigerant?” is Yes
Leak check methodChoose one
Shown when “Does this unit hold F gas refrigerant?” is Yes and “Was a leak check done on this visit?” is Yes
Result of the leak checkChoose one
Shown when “Does this unit hold F gas refrigerant?” is Yes and “Was a leak check done on this visit?” is Yes
Where was the leak?Short answer
Shown only when the answers above make it relevant
- WarningLeak found. The operator must have the leak repaired without undue delay. Where the unit is subject to leak checks, a certified person must check it within one month of the repair to confirm the repair worked.
Shown only when the answers above make it relevant
Refrigerant added (kg)Number
Shown when “Does this unit hold F gas refrigerant?” is Yes
Refrigerant recovered (kg)Number
Shown when “Does this unit hold F gas refrigerant?” is Yes
Photos after the workPhotos
Any defects on this unit?Yes or No
Describe the defectNotes
Shown when “Any defects on this unit?” is Yes
PriorityChoose one
Shown when “Any defects on this unit?” is Yes
How was the unit left?Choose one