Skip to main content

Form library · Facilities and maintenance

Schedule of test results template

An electrical test sheet for a distribution board. Record the supply, Ze or Zdb and prospective fault current and photos of the board, then each circuit with its protective device, cable sizes, continuity and ring readings, insulation resistance, polarity, measured and maximum Zs, RCD time and the test button. The form works out Ze + (R1 + R2) as a cross-check on the measured Zs, (r1 + r2) / 4 for a ring, and the measured Zs as a share of the maximum you enter from the BS 7671 tables or the manufacturer. It warns on insulation resistance under 1 MΩ at 500 V, Zs over the maximum and an RCD slower than 300 ms, flags a pass that does not match the readings, and counts circuits passed, failed and outside each limit. It is a site record of the readings, not the BS 7671 schedule itself. Try the form below, see every question or open a completed example.

Ready to use from the form library, and every question is yours to edit. Try it for a small trial fee, cancel any time.

Try it on your phone

Try it on this phone

Fill in the schedule of test results on your phone now

See how the schedule of test results looks on your phone

Scan the code with your phone camera. It opens the real form, no sign-up needed.

Open the live example and fill it in, just as your team would on site. No sign-up needed.

See it on this phone

Every question is editable. Add this form to your account, then change the wording, add or remove questions and options, and make it fit your own jobs.

Or start your trial with this form ready →

One email, and we won't add you to a mailing list.

What goes on a schedule of test results?

A schedule of test results records, for each circuit on a board, the circuit number and description, the protective device type and rating, the live and protective conductor sizes, continuity (R1 + R2, and r1, rn and r2 for a ring), insulation resistance live to live and live to earth with the test voltage, polarity, the maximum measured earth fault loop impedance Zs, the RCD disconnection time and the test button checks. The IET model schedule for BS 7671:2018+A4:2026 has these columns.

Last updated . Facts checked by the SiteSurvey team on 20 October 2026 against IET: BS 7671:2018+A4:2026 model forms, condition report and schedule of test results, IET: BS 7671 inspection and testing FAQs (insulation resistance test voltage), IET Wiring Matters: the 1 megohm minimum insulation resistance, IET Wiring Matters, July 2022: RCD operating times and GOV.UK: electrical safety standards in the private and social rented sectors.

Built for circuit by circuit test results

Record the board and supply, then each circuit's readings. The form works out Ze + (R1 + R2) and (r1 + r2) / 4 as cross-checks, shows the measured Zs as a share of the maximum you enter from the BS 7671 tables, warns on readings outside the limits it checks and counts circuits by result. It is a site record of the readings, not the BS 7671 schedule itself.

The completed schedule on a phone: 5 circuits tested, 3 passed, 2 failed, 1 with insulation under 1 MΩ at 500 V, 0 with Zs over the maximum, 1 RCD slower than 300 ms, highest Zs 57% of its maximum

Circuits counted against each limit

The form counts circuits tested, passed and failed, with insulation resistance under 1 MΩ at 500 V, Zs over the maximum entered and an RCD slower than 300 ms, and shows the highest Zs as a share of its maximum.

How calculated fields work →
Ring end to end readings rn 0.51 and r2 0.84 Ω, then the difference between r1 and rn 0.01 Ω and (r1 + r2) / 4 = 0.34 Ω, next to the measured R1 + R2 of 0.34 Ω

Ring readings worked out

For a ring final circuit, the form shows the difference between r1 and rn and works out (r1 + r2) / 4, the R1 + R2 you would expect at each socket, next to the reading you take.

How calculated fields work →
Continuity R1 + R2 0.41 Ω and the calculated Ze + (R1 + R2) of 0.62 Ω

Ze + (R1 + R2) beside the reading

From Ze or Zdb on page 1 and R1 + R2, the form works out Ze + (R1 + R2), a common cross-check on the measured Zs, and the measured Zs as a share of the maximum.

How calculated fields work →
Measured Zs 22% of the maximum, RCD operating time 312 ms, and a red note that IET guidance gives 300 ms as the maximum for a general non-delay RCD

Slow RCD flagged

An RCD over 300 ms at its rated residual current, insulation resistance under 1 MΩ at 500 V or Zs over the maximum brings up a red note, and a circuit marked as a pass with one of these gets an amber note.

How calculated fields work →

Film the board

Add photos of the board with its cover on and off, or a Walk Cam recording with spoken notes, so the record shows the board you tested.

A completed schedule of test results

A fictional joinery workshop board: five circuits, a ring with matching end to end readings, a dust extractor radial with 0.6 MΩ to earth left off and labelled, and a yard lighting RCBO that took 312 ms, recorded as a fail with a replacement booked.

An open grey distribution board on a blockwork wall in a joinery workshop with a row of RCBOs and a circuit chart in the door
DB1 · workshop entrance · cover off
A yellow multifunction installation tester with test leads on a workbench below the open board
Multifunction tester on the bench below DB1

Try the schedule of test results form live

Answer a few questions and watch it adapt. Your answers are not saved, and any photos you add are deleted within the hour.

Live form: Electrical Test Results ScheduleOpen full screen ↗
Fill it in right here

This is the real form as your team would use it: questions appear as you answer, scores work themselves out and you can add photos and signatures. No sign-up needed. Or open a completed example to see every answer, photo and score filled in.

Want to see one filled in? See a completed schedule of test results report (PDF), made by SiteSurvey from a fictional site visit.

Every question in the schedule of test results template

An electrical test results schedule for a distribution board: every circuit with its device, cables, continuity, insulation resistance, polarity, Zs and RCD times, with warnings on readings that fail. 3 sections and 61 questions. Follow-up questions and guidance appear only when an answer calls for them, so the person on site never sees the ones that do not apply.

Make it your own: every question is editable

This is a starting point, not a fixed form. Once it is in your SiteSurvey account you can reword any question, add or remove questions, sections and answer options, and add your own logo, so it fits the way your team works and the jobs you do.

Details you only enter once

Add this form to a project in SiteSurvey and it fills in what the project already knows, so nobody on site retypes it and every form on the job uses the same names. Anything filled in can still be changed.

  • Project: the project name
  • Client: the project's customer
  • Site: the site, when the form is opened for a space or a product
  • Site address: the site address, from the space or the project

Board and supply

  • ProjectShort answer
    Fills in from the project name
  • ClientShort answer
    Fills in from the project's customer
  • Site*Short answer
    Fills in from the site, when the form is opened for a space or a product
  • Site addressShort answer
    Fills in from the site address, from the space or the project
  • Date of the tests*Date
  • Tested by*Short answer
  • Distribution board reference and location*Short answer
  • Scan the board labelScan a label: asset number

    Optional. Scan the label or tag to capture its numbers.

  • Photos of the boardPhotos

    Optional. The board with its cover on and off, the circuit chart and anything you found.

  • Earthing arrangementChoose one
    • TN-C-S (PME)
    • TN-S
    • TT
    • Other
  • Earth fault loop impedance at the board, Ze or Zdb (Ω)Number

    Ze at the origin, or Zdb at a sub-distribution board.

  • Prospective fault current (kA)Number
  • Test instrument, serial number and calibration dateShort answer
  • CheckThis is a site record of the readings and checks. It is not the BS 7671 certificate or schedule itself: issue that from your registration scheme's or your certification software.

Circuits

  • Circuits tested
    Repeat for each circuit. Each one asks:
    • Circuit number*Short answer
    • Circuit description*Short answer
    • Points servedNumber
    • Live conductor (mm²)Number
    • Protective conductor (mm²)Number
    • Protective deviceChoose one
      • MCB type B
      • MCB type C
      • MCB type D
      • RCBO type B
      • RCBO type C
      • BS 88 fuse
      • BS 1361 fuse
      • BS 3036 rewireable fuse
      • Other
    • Rating (A)Number
    • RCD typeChoose one
      • Type AC
      • Type A
      • Type F
      • Type B
      • No RCD
    • Ring final circuit?Yes or No
    • Ring end to end r1 (Ω)Number
      Shown when “Ring final circuit?” is Yes
    • Ring end to end rn (Ω)Number
      Shown when “Ring final circuit?” is Yes
    • Ring end to end r2 (Ω)Number
      Shown when “Ring final circuit?” is Yes
    • Difference between r1 and rn (Ω)Worked out by the form
      Shown when “Ring final circuit?” is Yes and “Ring end to end r1 (Ω)” is answered and “Ring end to end rn (Ω)” is answered
    • (r1 + r2) / 4, the expected R1 + R2 for the ring (Ω)Worked out by the form
      Shown when “Ring final circuit?” is Yes and “Ring end to end r1 (Ω)” is answered and “Ring end to end r2 (Ω)” is answered
    • Continuity R1 + R2 (Ω)Number
    • Ze + (R1 + R2) (Ω)Worked out by the form

      Ze or Zdb from page 1 plus R1 + R2. Compare it with the measured Zs below.

      Shown when “Earth fault loop impedance at the board, Ze or Zdb (Ω)” is answered and “Continuity R1 + R2 (Ω)” is answered
    • Insulation resistance test voltageChoose one
      • 250 V
      • 500 V
      • 1000 V
    • Insulation resistance, live to live (MΩ)Number
    • Insulation resistance, live to earth (MΩ)Number
    • WarningBelow 1 MΩ. The IET gives 1 MΩ as the minimum insulation resistance, with a 500 V d.c. test for circuits up to 500 V. Investigate before the circuit is put into service.
      Shown only when the answers above make it relevant
    • PolarityChoose one
      • Correct
      • Fault
    • Earth fault loop impedance Zs, measured (Ω)Number
    • Maximum permitted Zs for this device (Ω)Number

      From the BS 7671 tables or the device manufacturer.

    • Measured Zs as a share of the maximum (%)Worked out by the form
      Shown only when the answers above make it relevant
    • WarningMeasured Zs is above the maximum permitted for this protective device. The device may not disconnect in time.
      Shown only when the answers above make it relevant
    • RCD operating time at rated residual current (ms)Number
    • WarningOver 300 ms at the rated residual current. IET guidance gives 300 ms as the maximum for a general non-delay RCD (an S type time-delayed RCD may take up to 500 ms). Check or replace the RCD.
      Shown only when the answers above make it relevant
    • RCD or AFDD test button operatesChoose one
      • Yes
      • No
      • Not fitted
    • Result*Choose one
      • Pass
      • Fail
    • CheckRecorded as a pass, but a reading above is outside a limit the form checks. Check the reading and the result.
      Shown only when the answers above make it relevant
    • ObservationsNotes
      Shown only when the answers above make it relevant
    • c_f_passWorked out by the form
    • c_f_failWorked out by the form
    • c_f_irWorked out by the form
    • c_f_zsWorked out by the form
    • c_f_rcdWorked out by the form
    • Circuit retest readingsAnswer

      Only when the circuit failed: one row per retest after the fix. Limits: insulation 1 MΩ (500 V test), RCD 300 ms (general non-delay). For a 250 V SELV or PELV test or an S type RCD, judge the result yourself.

      Shown only when the answers above make it relevant
  • Circuits testedWorked out by the form
  • Circuits passedWorked out by the form
  • Circuits failedWorked out by the form
  • Insulation under 1 MΩ at 500 VWorked out by the form
  • Zs over the maximumWorked out by the form
  • RCD slower than 300 msWorked out by the form
  • Highest Zs as a share of its maximum (%)Worked out by the form
    Shown only when the answers above make it relevant

Actions and sign-off

  • Are further actions needed?Yes or No
  • CheckA circuit failed, but no further action is recorded. Add what needs doing, who will do it and when.
    Shown only when the answers above make it relevant
  • Further actions
    Repeat for each action. Each one asks:
    Shown when “Are further actions needed?” is Yes
    • What needs doing?*Notes
    • Who will do it?Short answer
    • Due dateDate
    • StatusChoose one
      • Open
      • In progress
      • Completed
  • Inspector nameWorked out by the form
  • Position or company of the testerShort answer
  • Inspector signatureSignature
  • CheckSigning records what was found on the day. It is not a guarantee of condition and does not replace any examination, test, design check or repair needed from a competent person.

See it filled in

A completed schedule of test results report, made by SiteSurvey from a fictional site visit: every answer, the photos, the guidance that applied and the sign-off, ready to send as a PDF.

See completed form (PDF) ↗

Schedule of test results FAQs

What is the minimum insulation resistance?

The IET gives 1 MΩ as the minimum insulation resistance, with a 500 V d.c. test for circuits up to and including 500 V (other than SELV and PELV). The form shows a warning when either reading at 500 V is under 1 MΩ, so the circuit is investigated before it is put into service.

How does it check Zs?

Enter the measured earth fault loop impedance and the maximum permitted for that protective device, from the BS 7671 tables or the device manufacturer. The IET schedule asks you to note the source when the maximum is not from the BS 7671 tables. The form warns when the measured value is higher, because the device may not disconnect in time. It also shows Ze + (R1 + R2) next to the reading as a cross-check, and the measured Zs as a share of the maximum.

What about RCD tests?

Record the operating time from an alternating current test at the rated residual current. IET guidance gives 300 ms as the maximum for a general non-delay RCD, and 130 to 500 ms for an S type time-delayed RCD. The form warns over 300 ms, and records whether the RCD or AFDD test button works.

Is this the BS 7671 schedule itself?

No. It is a site record of the readings, so they are captured on the phone with the board and circuit details. Issue the formal certificate and schedule from your registration scheme's or your certification software.

Can I record ring final circuits?

Yes. Answer that the circuit is a ring and the form asks for the end-to-end r1, rn and r2 readings as well as R1 + R2. It shows the difference between r1 and rn and works out (r1 + r2) / 4, the R1 + R2 you would expect at each socket on a sound ring.

Who uses this?

Electricians testing new work, periodic inspections and remedial work, and facilities teams keeping results for each board. In England, private and social landlords must have the electrical installation inspected and tested at least every 5 years, and the report includes a schedule of test results.

Related

Use this schedule of test results form with your team

Add it from the form library in one click, change any question, and every completed form becomes a branded PDF report.

Start your trial →