Water supplyChoose one
Is there a cold water storage tank?Yes or No
Close-fitting lid and insect screens fitted?Yes or No
Shown when “Is there a cold water storage tank?” is Yes
Clean inside, with no sediment, scale or debris?Yes or No
Shown when “Is there a cold water storage tank?” is Yes
Tank and pipework insulated?Yes or No
Shown when “Is there a cold water storage tank?” is Yes
Temperature of the stored cold water (°C)Number
Shown when “Is there a cold water storage tank?” is Yes
Tank length (m)Number
Measure with a tape where you can. From a photo, use a door or an A4 sheet on the tank side as the reference: an estimate, good enough to check the size against the use.
Shown when “Is there a cold water storage tank?” is Yes
Tank width (m)Number
Shown when “Is there a cold water storage tank?” is Yes
Depth of water in the tank (m)Number
Shown when “Is there a cold water storage tank?” is Yes
Water stored (litres)Worked out by the form
Shown only when the answers above make it relevant
Estimated cold water use per day (litres)Number
Shown when “Is there a cold water storage tank?” is Yes
Days of use the tank holdsWorked out by the form
Shown only when the answers above make it relevant
- CheckThe tank holds more than a day's use. Water that stands for days can warm up and lose its disinfectant: note whether the tank is oversized for how the building is used now.
Shown only when the answers above make it relevant
- CheckAbove 20 °C. HSE guidance is to keep cold water below 20 °C. Check insulation, turnover and nearby heat sources.
Shown only when the answers above make it relevant
Photos of the tank, inside and outPhotos
Shown when “Is there a cold water storage tank?” is Yes
How is hot water made?Choose one
Stored hot water temperature (°C)Number
Shown only when the answers above make it relevant
- CheckBelow 60 °C. HSE guidance is to store hot water at 60 °C or more.
Shown only when the answers above make it relevant
Calorifier return temperature (°C)Number
Shown only when the answers above make it relevant
- CheckBelow 50 °C. HSE guidance (HSG274 Part 2) is for the return to the calorifier to be at least 50 °C, or 55 °C in healthcare premises.
Shown only when the answers above make it relevant
Are thermostatic mixing valves fitted?Yes or No
Are there showers, spray taps or other outlets that make a spray?Yes or No
Are there little-used outlets?Yes or No
Spare rooms, empty flats, outside taps, a shower nobody uses.
How are they flushed, how often, and who records it?Short answer
Shown when “Are there little-used outlets?” is Yes
Any dead legs or redundant pipework?Yes or No
Other systems on siteTick all that apply
- CheckCooling towers and evaporative condensers. The Notification of Cooling Towers and Evaporative Condensers Regulations 1992 require the person in control of the premises to notify the local authority in writing of these devices. This form does not cover them: they need their own assessment.
Shown when “Other systems on site” includes “Cooling tower or evaporative condenser”