IT maintenance checklist

A routine IT maintenance visit form for IT support engineers. It covers the comms or server room, the UPS, each server or storage device, backups, the firewall and network, anything about to expire and optional PC and laptop checks, then the outcome, parts and the customer's signature. The form checks the UPS runtime against what the site needs and the battery age against the maker's interval, counts the days an outstanding update has been out against 14, shows the internet speeds as a share of the contract and counts the servers and devices needing attention. Try the form below, see every question or open a completed example.

Ready to use from the form library, and every question is yours to edit. Try it for a small trial fee, cancel any time.

Try it on your phone

Try it on this phone

Fill in the IT maintenance on your phone now

See how the IT maintenance looks on your phone

Scan the code with your phone camera. It opens the real form, no sign-up needed.

Open the live example and fill it in, just as your team would on site. No sign-up needed.

See it on this phone

Every question is editable. Add this form to your account, then change the wording, add or remove questions and options, and make it fit your own jobs.

Or start your trial with this form ready →

One email, and we won't add you to a mailing list.

What should an IT maintenance checklist include?

An IT maintenance checklist should cover the server or comms room (security, temperature and cooling), the UPS (status, load, runtime, battery age and self test), each server (hardware alerts, disks, free space, updates and logs), backups and a restore test, firewall firmware, switches and Wi-Fi, and licences or warranties about to expire. It should end with the outcome, parts used and a signature.

Last updated . Facts checked by the SiteSurvey team on 21 October 2026 against NCSC Cyber Essentials: Requirements for IT Infrastructure v3.3 and NCSC on offline backups in an online world.

Built for IT engineers on a maintenance round

Work through the comms room, the UPS, each server, backups, the network and the PCs you checked. The form compares the UPS runtime with what the site needs and the battery age with the maker's replacement interval, counts the days an outstanding update has been out against the 14 days in Cyber Essentials, shows the measured internet speeds as a share of the contract, and counts the servers and devices that need attention.

Age of the batteries 5 years, maker's battery replacement interval 4 years, and the result Due for replacement

UPS batteries against the maker's interval

Enter the battery age and the replacement interval from the data sheet. The form says Within the interval, Due within a year or Due for replacement, and checks the runtime shown against the runtime the site needs to shut down cleanly.

How calculated fields work →
Release date of the oldest outstanding update 1 September 2026, 22 days since that update was released, Over 14 days

Update age against 14 days

Where a critical or high risk update is still outstanding, enter its release date. The form counts the days to the visit and flags anything over 14, the time Cyber Essentials allows for installing those updates.

How calculated fields work →
2 servers checked, 0 with a hardware warning or fault, 0 with disks degraded or failed, 0 under 15% free space, 0 no longer getting security updates, 1 with updates outstanding over 14 days

Servers that need attention, counted

The form counts the servers with hardware alerts, degraded or failed disks, low free space, no security updates and late updates, and does the same for the PCs and laptops you checked.

How calculated fields work →
Contracted download 160 Mbps and upload 30 Mbps, with download 91% and upload 93% of the contract

Speeds against the contract

Add the contracted speeds once and the measured download and upload show as a share of the contract, so a slow line is obvious in the report.

How calculated fields work →

The comms cabinet on video

Film the cabinet, UPS and cooling with a spoken note in the SiteSurvey app, so the next engineer sees how you left it.

How Walk Cam works →

A completed IT maintenance visit

A quarterly visit to a fictional Bath office: UPS batteries five years old against a four year interval, a NAS firmware update 22 days old booked for the evening, a laptop with 12% free space and the line at 91% of its contracted download speed. Open it as a filled-in form, or switch to a blank copy and try it yourself.

A rack mount UPS at the bottom of a wall cabinet with an amber battery warning on its display
UPS with a replace battery warning · batteries due for replacement
A wall mounted network cabinet with a switch, patch panel and UPS
Network cabinet in the open office · not locked

Try the IT maintenance form live

Answer a few questions and watch it adapt. Your answers are not saved, and any photos you add are deleted within the hour.

Live form: IT Maintenance VisitOpen full screen ↗
Fill it in right here

This is the real form as your team would use it: questions appear as you answer, scores work themselves out and you can add photos and signatures. No sign-up needed. Or open a completed example to see every answer, photo and score filled in.

Want to see one filled in? See a completed IT maintenance report (PDF), made by SiteSurvey from a fictional site visit.

Fill it in on a phone or tablet

Your team completes the it maintenance visit on site in the SiteSurvey app on iPhone, iPad and Android phones and tablets. The project name and address fill in for them, it works without signal, and it syncs when the device is back online with photos kept against the question they answer.

Customers and subcontractors do not need the app: send them a link and they can fill it in from any browser.

The IT Maintenance Visit form in the SiteSurvey app on a tablet
The IT Maintenance Visit form in the SiteSurvey app on a phone

Every question in the IT maintenance template

Routine IT maintenance visit: comms room, UPS runtime and battery age against the need, servers and storage, update age against 14 days, backups, speeds against the contract, PC checks, defects and sign-off. 9 sections and 98 questions. Follow-up questions and guidance appear only when an answer calls for them, so the person on site never sees the ones that do not apply.

Make it your own: every question is editable

This is a starting point, not a fixed form. Once it is in your SiteSurvey account you can reword any question, add or remove questions, sections and answer options, and add your own logo, so it fits the way your team works and the jobs you do.

Details you only enter once

Add this form to a project in SiteSurvey and it fills in what the project already knows, so nobody on site retypes it and every form on the job uses the same names. Anything filled in can still be changed.

  • Project: the project name
  • Customer: the project's customer
  • Site: the site, when the form is opened for a space or a product
  • Address: the site address, from the space or the project

Job details

The job and the site.

  • ProjectShort answer

    Filled in from the project in SiteSurvey.

    Fills in from the project name
  • Job or contract referenceShort answer
  • CustomerShort answer
    Fills in from the project's customer
  • Site*Short answer
    Fills in from the site, when the form is opened for a space or a product
  • AddressShort answer
    Fills in from the site address, from the space or the project
  • Date of visit*Date
  • Type of visit*Choose one
    • Planned maintenance
    • Call-out for a fault
    • Return visit
  • What was reported, and by whom?Notes
    Shown when “Type of visit” is “Call-out for a fault”
  • Reference of the earlier jobShort answer
    Shown when “Type of visit” is “Return visit”
  • Engineer nameShort answer

Comms or server room

The room the equipment lives in.

  • Is the room or cabinet locked?Yes or No
  • Temperature at the front of the cabinet (°C)Number
  • CheckThis is above 27 °C, the top of the ASHRAE recommended range for air going into IT equipment. Check the cooling and anything blocking the airflow.
    Shown only when the answers above make it relevant
  • CoolingChoose one
    • Working
    • Not working
    • None fitted
  • Is the room clean, dry and free of stored items?Yes or No
  • Any sign of water, leaks or pipes above the equipment?Yes or No
  • Photos of the room and cabinetPhotos

UPS

Battery backup for the servers and network.

  • Is there a UPS?Yes or No
  • UPS make and modelShort answer
    Shown when “Is there a UPS?” is Yes
  • Status on the displayChoose one
    • Normal
    • On battery
    • Alarm or fault showing
    • Replace battery warning
    Shown when “Is there a UPS?” is Yes
  • WarningTell the site contact now: the equipment could lose power without warning.
    Shown only when the answers above make it relevant
  • Load (%)Number
    Shown when “Is there a UPS?” is Yes
  • Runtime shown (minutes)Number
    Shown when “Is there a UPS?” is Yes
  • Runtime the site needs (minutes)Number

    Long enough to shut the servers down cleanly, as agreed with the customer.

    Shown when “Is there a UPS?” is Yes
  • Runtime against the needWorked out by the form
    Shown only when the answers above make it relevant
  • Age of the batteries (years)Number
    Shown when “Is there a UPS?” is Yes
  • Maker's battery replacement interval (years)Number

    From the UPS or battery data sheet. Leave blank if it is not known.

    Shown when “Is there a UPS?” is Yes
  • Battery age against the intervalWorked out by the form
    Shown only when the answers above make it relevant
  • Self testChoose one
    • Passed
    • Failed
    • Not run
    Shown when “Is there a UPS?” is Yes
  • Photo of the UPS displayPhotos
    Shown when “Is there a UPS?” is Yes
  • GuidanceUPS batteries wear out and the life depends on the type and the room temperature. Check the maker's replacement interval against the age you recorded.
    Shown when “Is there a UPS?” is Yes

Servers and storage

One entry for each server, NAS or host.

  • Are there servers or storage devices on site?Yes or No
  • Servers and storage
    Repeat for each server. Each one asks:
    Shown when “Are there servers or storage devices on site?” is Yes
    • Name*Short answer
    • What it doesShort answer
    • Scan the serial or asset labelScan a label: serial number, asset tag

      Optional. Scan the label or tag to capture its numbers.

    • Hardware lights and alertsChoose one
      • Normal
      • Warning
      • Fault
    • Disks or RAIDChoose one
      • Healthy
      • Degraded
      • Failed
    • WarningA degraded array has lost its protection: another disk failure could lose the data. Replace the disk and check the last backup before you leave.
      Shown only when the answers above make it relevant
    • Free disk space (%)Number
    • CheckUnder 15% free. Plan a clean up or more storage before it fills.
      Shown only when the answers above make it relevant
    • Does the operating system still get security updates?Choose one
      • Yes
      • No
      • Not known
    • WarningCyber Essentials requires software to be licensed and supported, and removed from devices when it becomes unsupported. Raise a replacement or upgrade with the customer.
      Shown when “Does the operating system still get security updates?” is “No”
    • Security updatesChoose one
      • Up to date
      • Installed on this visit
      • Outstanding
    • Release date of the oldest outstanding critical or high risk updateDate
      Shown when “Security updates” is “Outstanding”
    • Days since that update was releasedWorked out by the form
      Shown when “Security updates” is “Outstanding” and “Release date of the oldest outstanding critical or high risk update” is answered
    • Against 14 daysWorked out by the form
      Shown when “Security updates” is “Outstanding” and “Release date of the oldest outstanding critical or high risk update” is answered
    • Event logs reviewed?Yes or No
    • Anti-malware running and up to date?Yes or No
    • Errors found and action takenNotes
  • GuidanceUpdates. Cyber Essentials requires updates that fix critical or high risk vulnerabilities to be installed within 14 days of release.
    Shown when “Are there servers or storage devices on site?” is Yes
  • Servers checkedWorked out by the form
    Shown when “Are there servers or storage devices on site?” is Yes
  • Hardware warning or faultWorked out by the form
    Shown when “Are there servers or storage devices on site?” is Yes
  • Disks degraded or failedWorked out by the form
    Shown when “Are there servers or storage devices on site?” is Yes
  • Under 15% free spaceWorked out by the form
    Shown when “Are there servers or storage devices on site?” is Yes
  • No longer getting security updatesWorked out by the form
    Shown when “Are there servers or storage devices on site?” is Yes
  • Updates outstanding over 14 daysWorked out by the form
    Shown when “Are there servers or storage devices on site?” is Yes
  • Were user and admin accounts checked for leavers and accounts no longer needed?Choose one
    • Yes, none found
    • Yes, accounts disabled
    • Not checked

Backups

Whether the data could be brought back today.

  • Last backup job*Choose one
    • Completed
    • Completed with errors
    • Failed
    • No backup set up
  • Date of the last good backupDate
    Shown only when the answers above make it relevant
  • Days since the last good backupWorked out by the form
    Shown when “Date of the last good backup” is answered and “Date of visit” is answered
  • WarningThere is no working backup. Tell the customer today and record who you told.
    Shown only when the answers above make it relevant
  • Is there a copy off site or in the cloud?Yes or No
  • Did you restore a file as a test on this visit?Yes or No
  • Date of the last restore testDate
    Shown when “Did you restore a file as a test on this visit?” is No
  • Backup notesNotes

Network and subscriptions

Firewall, switches, Wi-Fi and anything about to expire.

  • Firewall firmwareChoose one
    • Up to date
    • Updated on this visit
    • Update outstanding
    • No longer supported
    • Not checked
  • SwitchesChoose one
    • OK
    • Defect
    • Not checked
  • Wi-FiChoose one
    • OK
    • Defect
    • Not checked
  • Internet speed, download (Mbps)Number
  • Internet speed, upload (Mbps)Number
  • Contracted download speed (Mbps)Number

    From the broadband or leased line contract. Leave blank to skip the comparison.

  • Contracted upload speed (Mbps)Number
  • Download as a share of the contract (%)Worked out by the form
    Shown only when the answers above make it relevant
  • Upload as a share of the contract (%)Worked out by the form
    Shown only when the answers above make it relevant
  • Is anything due to expire in the next 90 days?Yes or No

    Licences, warranties, domain names, certificates, support contracts.

  • What, and when?Notes
    Shown when “Is anything due to expire in the next 90 days?” is Yes

PCs and laptops

Optional: one entry for each device you check.

  • Did you check any PCs or laptops?Yes or No
  • Devices checked
    Repeat for each device. Each one asks:
    Shown when “Did you check any PCs or laptops?” is Yes
    • Device name or asset tag*Short answer
    • UserShort answer
    • UpdatesChoose one
      • Up to date
      • Installed on this visit
      • Outstanding
    • Release date of the oldest outstanding critical or high risk updateDate
      Shown when “Updates” is “Outstanding”
    • Anti-malwareChoose one
      • Running and up to date
      • Out of date
      • Not installed
    • Free disk space (%)Number
    • Cleaned: vents, keyboard, screen?Yes or No
    • Issues found and action takenNotes
  • Devices checkedWorked out by the form
    Shown when “Did you check any PCs or laptops?” is Yes
  • Updates outstandingWorked out by the form
    Shown when “Did you check any PCs or laptops?” is Yes
  • Anti-malware out of date or missingWorked out by the form
    Shown when “Did you check any PCs or laptops?” is Yes
  • Under 15% free spaceWorked out by the form
    Shown when “Did you check any PCs or laptops?” is Yes

Outcome and parts

How the system was left and what happens next.

  • Outcome of the visit*Choose one
    • No issues outstanding
    • Issues outstanding
    • Urgent issue outstanding
  • What needs doing next, and who will do it?Notes
    Shown only when the answers above make it relevant
  • RecommendationsNotes
  • Did you use any parts or materials?Yes or No
  • Parts and materials used
    Repeat for each part. Each one asks:
    Shown when “Did you use any parts or materials?” is Yes
    • ItemShort answer
    • Part numberShort answer
    • QuantityNumber
  • Next visit dueDate
  • Days to the next visitWorked out by the form
    Shown when “Date of visit” is answered and “Next visit due” is answered
  • CheckThe next visit date is before the date of this visit. Check the date.
    Shown only when the answers above make it relevant

Sign-off

Customer and engineer.

  • Is the customer or their representative available to sign?Yes or No
  • Why not, and who will you send the report to?Short answer
    Shown when “Is the customer or their representative available to sign?” is No
  • Customer nameShort answer
    Shown when “Is the customer or their representative available to sign?” is Yes
  • PositionShort answer
    Shown when “Is the customer or their representative available to sign?” is Yes
  • Customer commentNotes
    Shown when “Is the customer or their representative available to sign?” is Yes
  • Customer signatureSignature
    Shown when “Is the customer or their representative available to sign?” is Yes
  • Engineer nameWorked out by the form
  • Engineer signatureSignature

See it filled in

A completed IT maintenance report, made by SiteSurvey from a fictional site visit: every answer, the photos, the guidance that applied and the sign-off, ready to send as a PDF.

See completed form (PDF) ↗

IT maintenance FAQs

What does the UPS maintenance check cover?

The status on the display, the load, the runtime shown, the age of the batteries and the result of a self test. If the UPS is on battery, in alarm or asking for a battery replacement, the form tells the engineer to warn the site contact straight away. Battery life depends on the type and the room temperature, so enter the maker's replacement interval and the form shows whether the batteries are within it, due within a year or due for replacement. It also compares the runtime shown with the runtime the site needs to shut down cleanly.

What is checked on each server?

Hardware lights and alerts, disk or RAID status, free disk space, whether the operating system still gets security updates, the state of updates, event logs and anti-malware. A degraded or failed array shows a warning to replace the disk and check the last backup before leaving, and free space under 15% is flagged. The 15% figure is this form's own prompt.

How quickly should updates be installed?

Cyber Essentials requires updates that fix critical or high risk vulnerabilities to be installed within 14 days of release, and requires software to be removed from devices when it becomes unsupported. Where an update is outstanding, enter its release date and the form counts the days to the visit and flags anything over 14.

How does it check backups?

It records whether the last backup job completed, completed with errors or failed, the date of the last good backup and the days since, whether there is a copy off site or in the cloud, and whether a file was restored as a test on the visit, or when it last was. A failed or missing backup shows a warning to tell the customer today. The NCSC says backups should be tested regularly to check they work.

What temperature should a server room be?

The form records the temperature at the front of the cabinet and flags a reading above 27 °C, the top of the ASHRAE recommended range for air going into IT equipment. It also records whether the cooling is working and whether there is any sign of water near the equipment.

Does it work as a computer maintenance checklist too?

Yes. The PC and laptop page is optional, with an entry for each device: updates, anti-malware, free disk space, cleaning and any issues. The servers page is hidden if the site has none, so the same form suits a small office with only PCs and a router.