Form library · Facilities and maintenance

Chiller maintenance checklist

For maintenance technicians and people accepting chiller handback. Pin a roof chiller by GPS and measure the clearance in front of the condenser from a photo against the maker's manual. Enter the chilled water temperatures and the form works out the difference, its share of the design and whether the leaving water is within the allowed difference from the set point. It counts the service checks and the defects by priority. Try the form below, see every question or open a completed example.

Ready to use from the form library, and every question is yours to edit. Try it for a small trial fee, cancel any time.

Try it on your phone

Try it on this phone

Fill in the chiller maintenance on your phone now

See how the chiller maintenance looks on your phone

Scan the code with your phone camera. It opens the real form, no sign-up needed.

Open the live example and fill it in, just as your team would on site. No sign-up needed.

See it on this phone

Every question is editable. Add this form to your account, then change the wording, add or remove questions and options, and make it fit your own jobs.

Or start your trial with this form ready →

One email, and we won't add you to a mailing list.

Does a service record replace F gas duties?

GOV.UK describes leak-check and record-keeping duties for relevant F gas equipment. Requirements depend on the equipment and refrigerant. Identify the applicable regime and keep the required refrigerant records separately or by a clearly linked reference.

Last updated . Facts checked by the SiteSurvey team on 6 October 2026 against GOV.UK checking F gas equipment for leaks, GOV.UK recording F gas in equipment and HSE maintenance of work equipment.

Built for servicing chillers

Record the service at the chiller on a phone. Pin a roof unit, measure the clearance in front of the condenser from a photo, and enter the chilled water temperatures: the form works out the difference, compares the leaving water with the set point and counts the checks and the defects by priority. The set point, tolerances and design figures come from your controls schedule, commissioning record and the maker's manual; the form sets none.

Measured difference 5.1 K, 102% of the design difference, and leaving water Within the allowed difference from the set point

Chilled water against the set point

Enter the set point and allowed difference from the controls schedule, the design difference from the commissioning record and the two temperatures you read. The form works out the difference, its share of the design and whether the leaving water is within the allowance.

How calculated fields work →
Smallest clearance in front of the condenser air inlet measured from a photo as 0.32 m, with the marked-up photo kept under the field, and a minimum of 1.5 m from the maker's manual

Clearance in front of the condenser

Take a photo square on and measure the gap from it, using something of known size at the same distance. The form compares it with the maker's minimum, so stored materials blocking the air inlet are on the record. It works on web forms in any phone browser today, and the app version is on its way.

How measuring from a photo works →
Is the chiller on the roof or outside answered Yes, and Where is the chiller filled in with a GPS point, Mark again and View on map

Pin the chiller on the roof

For a roof or external unit, tap Mark current location beside it, so the next engineer goes straight to the right one. Mark current location works on web forms in any phone browser today, and the app version is on its way.

How GPS location works →
Counts worked out as 3 defects found: 0 urgent, 2 soon, 1 routine and 1 still open

Defects by priority

Log each defect with where it is, a photo and a priority. The form counts them by priority and shows how many are still open. An open urgent defect shows a red note to record how the chiller was left.

How calculated fields work →

Walk the plant with Walk Cam

Record a short clip at the pumps and the chiller and say what you found. The note is written down for you and kept with the visit.

How Walk Cam works →

A completed chiller maintenance record

A quarterly service of a fictional office's roof chiller: condenser coils and the return strainer cleaned after a low flow alarm, leaving water 7.2 °C against a 7 °C set point, and pallets of roofing slabs leaving 0.32 m in front of the coil against a 1.5 m minimum, reported to the facilities manager. Open it as a filled-in form, or switch to a blank copy and try it yourself.

A roof chiller beside a louvred plant screen with pallets of slabs in the gap, marked up with a measuring line from the coil to the pallets and a pallet as the reference
Clearance in front of the coil · about 0.32 m · minimum 1.5 m
An opened strainer on a chilled water pipe with its mesh basket on a rag, clogged with debris
Return strainer · cleaned after the low flow alarm
Leaves and debris caught in the condenser coil of a roof chiller
Circuit 2 condenser coil before cleaning

Try the chiller maintenance form live

Answer a few questions and watch it adapt. Your answers are not saved, and any photos you add are deleted within the hour.

Live form: Chiller MaintenanceOpen full screen ↗
Fill it in right here

This is the real form as your team would use it: questions appear as you answer, scores work themselves out and you can add photos and signatures. No sign-up needed. Or open a completed example to see every answer, photo and score filled in.

Want to see one filled in? See a completed chiller maintenance report (PDF), made by SiteSurvey from a fictional site visit.

Fill it in on a phone or tablet

Your team completes the chiller maintenance on site in the SiteSurvey app on iPhone, iPad and Android phones and tablets. The project name and address fill in for them, it works without signal, and it syncs when the device is back online with photos kept against the question they answer.

Customers and subcontractors do not need the app: send them a link and they can fill it in from any browser.

The Chiller Maintenance form in the SiteSurvey app on a tablet
The Chiller Maintenance form in the SiteSurvey app on a phone

Every question in the chiller maintenance template

A chiller maintenance record with equipment details, water circuit and refrigerant observations, operating readings, service work and handback limits. 6 sections and 78 questions. Follow-up questions and guidance appear only when an answer calls for them, so the person on site never sees the ones that do not apply.

Make it your own: every question is editable

This is a starting point, not a fixed form. Once it is in your SiteSurvey account you can reword any question, add or remove questions, sections and answer options, and add your own logo, so it fits the way your team works and the jobs you do.

Details you only enter once

Add this form to a project in SiteSurvey and it fills in what the project already knows, so nobody on site retypes it and every form on the job uses the same names. Anything filled in can still be changed.

  • Project: the project name
  • Site or premises address: the site address, from the space or the project
  • Client or organisation: the project's customer
  • Manufacturer, model and serial number: the product's model

Record details and scope

  • ProjectShort answer

    Filled in from the project in SiteSurvey.

    Fills in from the project name
  • Site or premises addressShort answer
    Fills in from the site address, from the space or the project
  • Client or organisationShort answer
    Fills in from the project's customer
  • Record date*Date
  • Person completing the record*Short answer
  • CheckFor competent chiller technicians using the manufacturer procedure. This record does not calculate statutory leak-check intervals, authorise refrigerant handling or replace pressure-system examinations.
  • CheckChillers holding F gas are covered by the retained Regulation (EU) No 517/2014 on fluorinated greenhouse gases: article 4 sets leak check intervals by tonnes CO2 equivalent (every 12 months from 5 tonnes, 6 months from 50 tonnes, 3 months from 500 tonnes, doubled where a leak detection system is fitted) and article 6 requires the operator to keep records for at least 5 years. Where the refrigerant circuit is a pressure system, the Pressure Systems Safety Regulations 2000 require a written scheme of examination and examinations by a competent person. BS EN 378 (Refrigerating systems and heat pumps, safety and environmental requirements) covers maintenance and repair. Keep the refrigerant records separately or by a clearly linked reference.

Equipment and work

  • Chiller asset ID and location*Short answer
  • Is the chiller on the roof or outside?Yes or No
  • Where is the chiller?Short answer

    Mark it standing beside the unit, so the next engineer goes straight to the right one. Tap Mark current location at the unit. It saves the coordinates, a grid reference and the accuracy.

    Shown when “Is the chiller on the roof or outside?” is Yes
  • Smallest clearance in front of the condenser air inlet (m)Number

    Air-cooled chillers only. Measure from a photo taken square on, using a door or the unit height from the data sheet as the reference. It is an estimate; close to the minimum, use a tape.

    Shown when “Is the chiller on the roof or outside?” is Yes
  • Minimum clearance in the maker's manual (m)Number
    Shown when “Is the chiller on the roof or outside?” is Yes
  • Clearance against the manualWorked out by the form
    Shown when “Is the chiller on the roof or outside?” is Yes and “Smallest clearance in front of the condenser air inlet (m)” is answered and “Minimum clearance in the maker's manual (m)” is answered
  • CheckLess clearance than the maker asks for. Warm air can recirculate into the condenser. Record what is in the way and who was told.
    Shown when “Clearance against the manual” is “Less than the manual”
  • Manufacturer, model and serial number*Short answer
    Fills in from the product's model
  • Scan the data plateScan a label: serial number, model number, asset number

    Optional. Scan the label or data plate to capture the serial and other numbers.

  • Maintenance procedure and revision*Short answer
  • Technician and competence reference*Short answer
  • Planned work and exclusions*Notes
  • Safe isolation or permit reference*Short answer

System information

  • Refrigerant type and charge from equipment recordsShort answer
  • F gas register and leak-check referenceShort answer
  • Water circuit, treatment and set-point referencesShort answer
  • Operating hours and reported alarmsShort answer

Service checks

  • Heat exchangers and air paths checked to procedure*Choose one
    • Acceptable
    • Action needed
    • Not checked
    • Not applicable
  • Action, limitation or reason not applicable*Notes
    Shown only when the answers above make it relevant
  • Water flow, strainers and visible leaks checked*Choose one
    • Acceptable
    • Action needed
    • Not checked
    • Not applicable
  • Action, limitation or reason not applicable*Notes
    Shown only when the answers above make it relevant
  • Compressor condition and oil observations recorded where applicable*Choose one
    • Acceptable
    • Action needed
    • Not checked
    • Not applicable
  • Action, limitation or reason not applicable*Notes
    Shown only when the answers above make it relevant
  • Controls, alarms and safety devices checked to procedure*Choose one
    • Acceptable
    • Action needed
    • Not checked
    • Not applicable
  • Action, limitation or reason not applicable*Notes
    Shown only when the answers above make it relevant
  • Checks acceptableWorked out by the form
  • Needing actionWorked out by the form
  • Not checkedWorked out by the form
  • GuidanceChilled water temperatures Take them with the chiller running steadily. The set point, allowed difference and design figure come from the controls schedule and the commissioning record; the form sets none.
  • Leaving chilled water set point (°C)Number
  • Allowed difference from the set point (± K)Number
  • Measured leaving chilled water (°C)Number
  • Measured entering (return) chilled water (°C)Number
  • Design entering to leaving difference (K)Number
  • Measured difference (K)Worked out by the form
    Shown when “Measured leaving chilled water (°C)” is answered and “Measured entering (return) chilled water (°C)” is answered
  • Share of the design difference (%)Worked out by the form
    Shown only when the answers above make it relevant
  • Leaving water against the set pointWorked out by the form
    Shown when “Measured leaving chilled water (°C)” is answered and “Leaving chilled water set point (°C)” is answered and “Allowed difference from the set point (± K)” is answered
  • CheckLeaving water is outside the allowed difference. Record the cause and what was done in the readings or defects below.
    Shown when “Leaving water against the set point” is “Outside”
  • Other measured values
    Repeat for each measured value. Each one asks:
    • Measurement point and parameter*Short answer
    • Actual value and unit*Short answer
    • Acceptance range and source*Short answer
    • Instrument ID and calibration referenceShort answer
    • Assessment*Choose one
      • Within criterion
      • Outside criterion
      • Unable to assess
    • Response to exception*Notes
      Shown only when the answers above make it relevant
  • Defects found
    Repeat for each defect. Each one asks:
    • Where on the chiller*Short answer
    • Defect*Notes
    • Priority*Choose one
      • Urgent: make safe or restrict use now
      • Soon: before the next visit
      • Routine: at the next planned visit
    • Put right on this visit?Yes or No
    • What happens next, and whoNotes
      Shown when “Put right on this visit?” is No
    • Photos of the defectPhotos
  • Defects foundWorked out by the form
  • UrgentWorked out by the form
  • SoonWorked out by the form
  • RoutineWorked out by the form
  • Still openWorked out by the form
  • WarningAn urgent defect is still open. Record on the next page how the chiller was left (restricted or out of service) and who on site was told before you leave.
    Shown only when the answers above make it relevant

Work and handback

  • Work performed and parts usedNotes
  • Post-work tests and evidenceNotes

    Record the authorised test, operating conditions and result against the specified criterion. Do not turn one reading into a general performance guarantee.

  • Equipment handback*Choose one
    • Available within recorded limits
    • Restricted use
    • Out of service
  • Restrictions, isolation and person informed*Notes
    Shown only when the answers above make it relevant
  • Condition and work evidence photosPhotos

Actions and review

  • Are further actions required?*Choose one
    • Yes
    • No
  • Further action
    Repeat for each further action. Each one asks:
    Shown when “Are further actions required?” is “Yes”
    • Action and evidence reference*Notes
    • PriorityChoose one
      • Urgent
      • High
      • Medium
      • Low
    • Person responsible*Short answer
    • Target dateDate
    • Action status*Choose one
      • Open
      • In progress
      • Completed
    • Completion evidence*Notes
      Shown when “Action status” is “Completed”
  • Outstanding limitations and information to pass onNotes
  • Record status*Choose one
    • Ready for review
    • Further work needed
    • Work or use stopped
  • Reviewed byShort answer
  • Review dateDate
  • Next service dueDate

    Set by the maintenance schedule or the manufacturer.

  • Days to next serviceWorked out by the form
    Shown when “Record date” is answered and “Next service due” is answered
  • CheckThe next due date is before the date of this record. Check the date entered.
    Shown only when the answers above make it relevant
  • Next F gas leak check dueDate

    Set from the charge in tonnes CO2 equivalent under article 4 of the F gas regulation.

  • Days to next leak checkWorked out by the form
    Shown when “Record date” is answered and “Next F gas leak check due” is answered
  • CheckThe next due date is before the date of this record. Check the date entered.
    Shown only when the answers above make it relevant
  • Author signature*Signature
  • CheckSigning records the information entered. It does not itself certify legal compliance, remove a limitation or authorise unsafe work.

Scope and responsibility

For competent chiller technicians using the manufacturer procedure. This record does not calculate statutory leak-check intervals, authorise refrigerant handling or replace pressure-system examinations.

What a useful entry looks like

Post-work tests and evidence

Record the authorised test, operating conditions and result against the specified criterion. Do not turn one reading into a general performance guarantee.

Functional check recorded under procedure CH-12. Operating conditions and readings are attached; seasonal performance was outside this visit's scope.

Fictional example of record wording. Use the actual evidence and approved arrangements for your job; this is not a completed report or an instruction to carry out the work.

See it filled in

A completed chiller maintenance report, made by SiteSurvey from a fictional site visit: every answer, the photos, the guidance that applied and the sign-off, ready to send as a PDF.

See completed form (PDF) ↗

Chiller Maintenance FAQs

How should I record “Post-work tests and evidence”?

Record the authorised test, operating conditions and result against the specified criterion. Do not turn one reading into a general performance guarantee.

Which readings can I record?

The chilled water temperatures have their own section: enter the set point, allowed difference and design difference from the controls schedule and commissioning record, and the form works out the rest. Add pressures, electrical readings or other parameters under Other measured values, each with a unit, acceptance source and instrument reference.

Are refrigerant limits supplied?

No. Enter the correct equipment data and applicable requirements; the form does not assume one refrigerant or jurisdiction.

What distinguishes this from a general HVAC visit?

It adds chiller identification, water-circuit details, refrigerant record references and repeatable operating measurements.

What are the limits of this template?

For competent chiller technicians using the manufacturer procedure. This record does not calculate statutory leak-check intervals, authorise refrigerant handling or replace pressure-system examinations.

Can I complete this form on site and share the record?

In the SiteSurvey app the form works offline, with photos and signatures recorded against the questions. Share the completed record as a PDF or a link. Dates and action owners are recorded fields; this form does not send reminders or update other systems.

Related